home | email  












Applied Learning Associates, Inc.
Tom Piscitelli
2146 NW Boulder Way Drive
Issaquah, WA 98072
phone: 425-985-4534
fax: 425-642-8172
email: Tom

 

 

Venting Today - A Complex Subject

by Tim McElwain


 Part 1 of 2  

The days of the old galvanized flue pipe vented into a masonry chimney lined or unlined are quickly fading away. It will not be long unit even Type “B” double wall gas vent will be a thing of the past.

With increased efficiencies in equipment the requirements for “special venting” are now in place, and venting requirements for 90+ efficiency products are likely to continually change.

Warnings like this in Installation and Operation manuals are commonplace:

WARNING

FAILURE TO VENT THIS BOILER IN ACCORDANCE WITH THESE INSTRUCTIONS COULD CAUSE FLUE GAS TO ENTER THE BUILDING RESULTING IN SEVERE PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH:

• Do not attempt to vent this boiler with galvanized, PVC, or any other vent system not listed in the instructions.
• Do not attempt to mix components from different approved vent systems.
• Do not obtain combustion air from within the building.
• Do not install a barometric damper or drafthood on this equipment.

CAUTION

Moisture and ice may form on the surface around the vent termination.

In talking to manufacturers reps about problems they discover on new installations they tell me that most are improperly vented due to failure to read the installation directions. We all know what INSTALLATION INSTRUCTIONS are…we use them to set our coffee cups and soda cans on so we don’t mark the equipment!

I am not going to attempt to teach Category IV 90+ Modulating Condensing venting here. I simply want to point out some of the typical things to watch out for. It is first of all imperative that directions be followed. Here are some of the things most manufacturers have in their instructions.

A lot of equipment today will list several different ways to vent their product:

1. Horizontal Side Wall Concentric Vent – the vent exits the building through the outside wall. Concentric pipe is a “pipe within a pipe”. Flue gas exits through the inside pipe, air for combustion is drawn in around the space between the inner and outer pipe.

2. Horizontal Side Wall Double Pipe (Separate flue gas pipe out and another pipe for air in)

3. Vertical Double Pipe vent exits the building through the roof. (Separate flue gas pipe out and another pipe for air in)

In some cases they may be direct vent or they may be classified mechanical exhausting. There are different requirements for those as to termination outside the building. We will cover some of those later in one of the other parts of this article.

Two basic categories:

1. Concentric

2. Double Pipe (Separate flue gas pipe out and another pipe for air in)

There are usually requirements for maximum vent and air intake lengths as well as in some cases minimum lengths.

Vent terminals vary with manufacturers and are not interchangeable from manufacturer to manufacturer.

The most difficult and often the most troublesome is the vent termination itself. This will be covered next month in Part 2 of Venting Today – A Complex Subject.

These technical manuals are now available:

• Circuitry and Troubleshooting Volume I and Volume II. $75.00 for Volume I and $35.00 for Volume II + $10.00 S/H.

• New Edition of FUNDAMENTALS OF GAS VOLUME I. $75.00 + $10.00 S/H.

• FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. $75.00 + $10.00 S/H.

We also conduct seminars on the following topics and many others:

• Fundamentals of Gas

• Circuitry and Troubleshooting

• Hydronic Controls

• Electric Ignition Systems

• Advanced Electric Ignition Systems

• Powerpile Systems

• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

For information call Tim McElwain at 401-437-0557, email him at gastc@cox.net, or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
 

Venting Today - A Complex Subject

by Tim McElwain


 Part 1 of 2  

One of the most difficult and often troublesome aspects of the new venting when venting out the side of buildings or even through the roof is vent termination or vent location. When we go to the code books it gets very detailed for example in the National Fuel gas Code ANSI Z223.1/NFPA 54 section 12.3.5 for direct vent appliances and concerning termination of direct vent section 12.9.3.

For Mechanical Exhausting the rules for termination are different as per section 12.4.3.6 concerning no vent terminating less than 7 feet above grade where located adjacent to public walkways.

Many times the Direct Vent rules and the Mechanical Exhausting rules get mixed up and incorrect venting termination occurs. Section 12.9 Through the Wall vent Termination covers all aspects of both direct vent (12.9.3) and mechanical exhausting (12.9.1 and 12.9.2) We will address those in Part Three of this article.

Some of the typical requirements:

  • Vent terminal must be at least 1 foot from any door, window, or gravity inlet into the building.
     

  • The double pipe (Example: The vent and air intake terminals must be at the same height and their center lines must be between 12 and 36 inches apart. Both terminals must be on the same wall)
     

  • All terminal bottoms must be 12 inches above normal snow line or no less than 12 inches above grade. (Note: it is often difficult to determine normal snow line)
     

  • 7 feet above public walkway
     

  • Do not install directly above windows or doors
     

  • The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.
     

  • A horizontal distance of at least 4 feet between the vent terminal and gas meters, electric meters, regulators and relief equipment. Do not install vent terminal over this equipment dues to condensate.
     

  • Do not locate vent under decks.
     

  • Top of vent terminal must be at least 5 feet below eves, soffits, or overhangs. Maximum depth of overhang is 3 feet.
     

  • Vent terminal must be 6 feet from an inside corner.
     

  • Be aware that condensate may freeze and cause damage to structures nearby.
     

  • Install vent termination away from prevailing winds in excess of 40 MPH.
     

  • Air intake must not be near possible combustion air contaminants.

These are some of the termination rules for sidewall venting. When vertical termination is allowed there are other rules these will be covered in Part Three in next month’s Sales Bytes.

We are now offering our latest manuals Circuitry and Troubleshooting Volume I and Volume II. They are selling for $75.00 for Volume I and $35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a copy + $10.00 shipping and handling. In addition we also have FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. It is also being offered at a price of $75.00 + $10.00 shipping and handling.

We also conduct seminars on the following topics and many others:

  • Fundamentals of Gas

  • Circuitry and Troubleshooting

  • Hydronic Controls

  • Electric Ignition Systems

  • Advanced Electric Ignition Systems

  • Powerpile Systems

  • NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

If you are interested in information call 401-437-0557 or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net

Venting Today - A Complex Subject

by Tim McElwain

 Part 3 of 5  

This is the final article on the minimum venting including requirements and exclusions.


As was mentioned in Part two we want to address the code requirements for vent termination. We are looking at the National Fuel Gas Code ANSI Z223.1/NFPA 54 2006 version and also the International Fuel Gas Code 2006 version.

This section will cover some of the code requirements, which must be addressed by manufacturers when setting down the rules for installation. The code rules can be added to but never made less severe in their application. It is however important note that manufacturers installation requirements have precedence.

In the NFPA 54 code this is addressed in Section 12.9 on page 54-102. In the IFGC section 503.8 page 85. There is also a reference to and Appendix “C” which is an illustration showing the application of some of these rules.

To keep it simple we will refer to the NFGC section 12.9, keep in mind the international code in this instance is exactly the same as the national. I have also removed the metric measurements for simplicity.

12.9 Through the Wall Vent Termination.

Section 12.9 provides requirements for separation of the termination point of the venting systems from the building openings for venting systems that terminate through the side of the building. The concern is for recirculation of products of combustion back into the building. There is also the possibility of cross contamination of the fresh intake air for combustion to the equipment.

12.9.1 A mechanical draft venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.

Exception No. 1: This provision shall not apply to the combus¬tion air intake of a direct-vent appliance.

The intent of 12.9.1 is to prevent gases from being drawn back into the building. This requirement recognizes that vent gases are lighter than air. Exception No. 1 recognizes that direct vent appliance inlets do not communicate with air in a building.

Exception NO.2: This provision shall not apply to the separation of the integral outdoor air inlet and flue gas discharge of listed outdoor appliances.

Exception No. 2 to 12.9.1 prevents confusion in the installation of outdoor gas appliances. Some authorities have misinterpreted the code to prohibit such appliances or to require them to be modified in the field, which is not the intent of 12.9.1. An example of this type of appliance is a packaged rooftop air conditioner, which incorporates a gas vent and a circulation air inlet used for building air supply.


12.9.2 A mechanical draft venting system of other than direct-vent type shall terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, operable window, or gravity air inlet into any building. The bottom of the vent terminal shall be located at least 12 inches above grade.

A question that often comes up concerning section 12.9.2 is do the separation requirements for exit terminals apply to windows that do not open? In the 1992 revision to the code the word “window” was replaced with “operable window”. This came about as a question pertaining to picture windows, which do not open. So the section does not apply to any windows, which cannot be opened.

12.9.3 The vent terminal of a direct-vent appliance with an input of 10,000 Btu/hr or less shall be located at least 6 inches from any air opening into a building, and such an appliance with an input over 10,000 Btu/hr but not over 50,000 Btu/hr shall be installed with a 9 inch vent termination clearance, and an appli¬ance with an input over 50,000 Btu/hr shall be at least a 12 inches vent termination clearance. The bot¬tom of the vent terminal and the air intake shall be located at least 12 in. (300 mm) above grade.

Sections 12.9.1 and 12.9.2 are concerned with preventing equipment combustion products from being drawn into a building through fresh air inlets, including operable windows (windows which can be opened).

Subsection 12.9.3 permits the vent terminals of direct vent appliances to be located much closer to air inlets than is provided for with mechanical draft equipment. There is often a mis application of rules for mechanical draft to direct vent equipment. The vent gases from direct vent equipment disperse rapidly upon leaving the vent terminal, even when the terminal is located under an open window. However, a window is unlikely to be open when heat is needed.

12.9.4 Through-the-wall vents for Category II and Category IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that condensate is a problem with Category I and Category III appliances, this provision shall also apply.

Subsection 12.9.4 provides for the protection of persons and equipment, including gas meters. It places responsibility on the installer to locate vent termination for Category II and Category IV appliances away from walkways and gas equipment. It also recognizes that any appliance can present a condensation problem in a cold climate.

High-efficiency condensing appliances have a seasonal efficiency of 90 percent or higher, which reduces vent gas temperatures to a point where the water vapor produced as a product of combustion condenses to liquid water in the appliance or in the vent. These condensing appliances carry a vented appliance category of Category IV. This type of appliance produces much cooler vent gases, resulting in water condensing in the vent. Venting must be accom¬plished with a fan, because the vent gases are not hot enough to operate the natural draft vent. Water will condense in the vent and will dissolve some of the gases produced during combustion, which are slightly acidic. The vent materials used with these appliances must be able to resist the acidic condensate. For many of these Category IV appliances, plastic vent material is acceptable and preferred for corrosion reasons. The appliance manufacturer specifies the vent material for use with Category IV appliances.

The advantage of high-efficiency appliances is that they significantly reduce the amount of gas consumed with no loss in output. A mid-efficiency appliance uses one-third less gas than a conventional appliance, and a condensing appliance uses only one-half of the gas of a conventional appliance. The savings in fuel are offset by higher first cost and the higher maintenance requirements of high-efficiency appliances, as well as the added cost of the electricity to operate the fan.

In the next part (Part 4) we will address other requirements for venting in particular vertical venting.

In part 5 we are going to address the venting categories mentioned in this article.

We are now offering our latest manuals Circuitry and Troubleshooting Volume I and Volume II. They are selling for $75.00 for Volume I and $35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a copy + $10.00 shipping and handling. In addition we also have FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. It is also being offered at a price of $75.00 + $10.00 shipping and handling.


We also conduct seminars on the following topics and many others:

• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

If you are interested in information call 401-437-0557 or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net
 

Venting Today - A Complex Subject

by Tim McElwain

 Part 4  

With this continuing discussion on venting of Modulating/Condensing equipment it is once again not the purpose of this article to define exact installation requirements. The attempt here is to address some typical types of requirements for venting this equipment.

When vertical venting is an option on this equipment it is important to follow manufacturers rules as to EQUIVALENT LENGTH as it relates to air intake of vent. An example would be:

90-degree concentric elbow 4.5 feet
45-degree concentric elbow 4 feet
A 3” 90 degree elbow 5.5 feet
A 3” 45 degree elbow 4 feet

Many times failure to observe these equivalent lengths in calculating the maximum length of the vent can result in inadequate air supply or problems with the pressure switch not making. It is often a good idea if the system will not work with the vent connected to remove the vent temporarily and see if the equipment will operate with it disconnected. If it will and it will not work with it connected you obviously have a problem with the vent. One of the things to address is length and also equivalent lengths of fittings. There may also be other problems such as blockage or damage to the vent.

There may also be other requirements addressed in the following examples:

Permitted Terminals for Vertical Venting - A straight termination is installed in the end of the vent pipe. The air inlet terminal consists of a 180-degree elbow (or two 90 degree elbows) with a rodent screen. Vent manufacturer part numbers for these screens vary.

Vertical Vent Terminal Locations - Observe the following limitations on the location of all vertical vent terminals.

• The top of the vent pipe must be at least 2 feet above any object located within 10 feet.

• The vertical distance between top of the vent and air inlet terminal openings must be at least 12".

• The bottom of the air inlet terminal must be at least 12" above the normal snow accumulation that can be expected on the roof.

• The air intake terminal must be located on the roof and must be no further than 24" horizontally from the exhaust pipe.

Wall thimbles - Wall thimbles are often required where single wall vent pipe passes through combustible walls.

Pitch of Horizontal Piping - Pitch all horizontal piping so that any condensate, which forms in the piping, will run towards the boiler:

• Pitch horizontal concentric venting 5/8" per foot

• Pitch Stainless steel venting 1/4" per foot.

Supporting Pipe - Vertical and horizontal sections of pipe must be properly supported:

• Support concentric venting near the female end of each straight section of pipe.
• Support stainless steel venting as called for by the vent manufacturer's instructions.

The next article on this topic will cover some of the code requirements, which must be addressed by manufacturers when setting down the rules for installation. The code rules can be added to but never made less severe in their application. It is however important to note that manufacturers installation requirements have precedence.


We are now offering our latest manuals Circuitry and Troubleshooting Volume I and Volume II. They are selling for $75.00 for Volume I and $35.00 for Volume II + $10.00 shipping and handling.

We have two OTHER NEW manuals in their second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a copy + $10.00 shipping and handling. In addition we also have FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. It is also being offered at a price of $75.00 + $10.00 shipping and handling.

We also conduct seminars on the following topics and many others:

• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

If you are interested in information call 401-437-0557 or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net
 

Venting Today - A Complex Subject

by Tim McElwain

 Part 5  

You can use the chart below to determine the equipment’s venting category. Look at the equipment’s rating plate and then proceed down that column to determine requirements and perimeters for venting that particular category. For example, a listed Category I appliance can be vented using a Type B gas vent, chimney, single-wall metal pipe, chimney lining system that is listed for gas venting, or a special gas vent listed for the appliance. The chart refers to appliance Category I through Category IV. The categories are based on vent temperature and pressure.

The term non-positive vent (negative pressure) means that even if fans or blowers are used in an appliance or vent system, venting is accomplished by natural draft. Natural draft is created by temperature difference (delta T) and the height of the vent. (The vent pressure is lower than atmospheric).

The term positive vent pressure means that fans, blowers or other means are used to propel vent gases through the vent at above atmospheric pressure.

Note that the definitions reference "a vent gas temperature that may cause excessive condensate production in the vent.") A specific temperature is not provided, because it is not the same for all appliances. The ANSI Z21 standards for appliance categorization can be referenced for this information. Annex L contains a complete list of the ANSI Z21 standards. Note that the installer should not need this information, since the appliance vent category is included in the appliance manufacturer's installation instructions and on the appliance nameplate. The criteria in the ANSI Z21 standards are based on a flue loss of 17 percent of total energy. The 17 percent flue loss is the same flue loss built into the vent sizing tables for fan-assisted appliances. In this way, the standards ensure that the appliance will work properly with the vent system. The term nonpositive vent pressure means that the pressure in the vent will be lower than the surrounding atmosphere if the vent system meets the requirements of the National Fuel Gas Code Chapter 12 and Chapter 13. The incorporation of a fan into the appliance does not always mean that the vent pressure is positive. If unsure, check the appliance nameplate or manufacturer's instructions for the venting category, or check the vent pressure with a manometer or other pressure gauge when the appliance is operating.

 

VENTING CATEGORIES:

GAS-FIRED EQUIPMENT

Operating

 

 

 

 

 

characteristics

Category I

Category II

Category III

Category IV

Pressure in the vent

Negative

Negative

Positive

Positive

Temperature of

Above

Below

Above

 

Below

vent gas (4)

275°F

275°F

275°F

 

275°F

Annual efficiency

Below 84%

Above 84%

Below 84%

Above 84%

Condensation

Not acceptable

Possible

Possible

In heat

 

(1)

(in vent)

(3)

 

exchanger

Design requirements

 

 

 

 

Gas (air) tight vent

No

No

Yes

 

Yes

Corrosion-resistant

No (1)

Yes

Possible

(3)

Yes

vent (water tight)

 

 

 

 

 

Vent into

Permitted

No

No

 

No

masonry chimney

(1) and (2)

 

 

 

 

Combined venting

Permitted

No

No

 

No

Condensate drain

No

Ask

Possible

(3)

Yes

 

 

manufacturer

 

 

(At

 

 

 

 

 

equipment)

Source of

N.F.G.C.

Manufact.

Manufact.

Manufact.

information

Fuel gas code,

literature

literature

literature

heating equipment

 

 

 

 

 

and vent system

 

 

 

 

 

manufacturers

 

 

 

 


NOTE 1 Usually, there is no problem when high vent gas temperature equipment is vented into double-wall vent or into a lined masonry chimney; but condensation could occur if mid-efficiency (80% to 84%) mechanical draft equipment is vented into a vent that has highly conductive walls, cold walls, or massive walls. In this case, design a vent system that minimizes the wall losses (use double-wall pipe for the whole run and avoid long runs through cold spaces).

NOTE 2 Install either a rigid or flexible metal liner inside of the masonry chimney and use a double-wall connector when venting mid-efficiency (80% to 84%), me¬chanical draft equipment.

NOTE 3 Condensation in the vent is posing on the ambient temperature and the conductivity of the vent walls. In this case, design a vent system that minimizes the wall losses (use insulated pipe and avoid long runs through cold spaces). A corrosion-resistant flue and a drain may be required if condensation cannot be prevented - refer to the manufacturer's recommendations.

NOTE 4 The dewpoint of the vent gas depends on the fuel (natural or LP gas), the amount of excess air and the amount of dilution air. The limiting case occurs when the dewpoint of the vent gas is at a maxi¬mum, which is about 135°F. This maximum is produced when natural gas is burned with no excess air or dilution air. There¬fore 275°F = 135°F dewpoint + 140°F

It is a good rule of thumb when looking at vent temperature that any temperature from 300° (F) down is a concern for condensing and needs to be addressed in the case of Category I and III venting.

We are now offering our latest manuals Circuitry and Troubleshooting Volume I and Volume II. They are selling for $75.00 for Volume I and $35.00 for Volume II + $10.00 shipping and handling.

We have two OTHER NEW manuals in their second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a copy + $10.00 shipping and handling. In addition we also have FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. It is also being offered at a price of $75.00 + $10.00 shipping and handling.

We also conduct seminars on the following topics and many others:

• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

If you are interested in information call 401-437-0557 or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net
 

Venting Today - A Complex Subject December 2007 issue

by Tim McElwain

 Part 6  

Plastic Piping:

• The Code
• Product Recall
• The Effects of Temperature on PVC pipe

National Fuel Gas Code specifies that plastic piping used for venting appliances listed for use with such venting materials shall be approved.

Before the introduction of high-efficiency (90 + percent efficiency) gas utilization equipment, plastic piping was prohibited as a vent material. High-efficiency (Category IV) appliances reduce vent temperatures, resulting in condensate formation. As accumulation of condensate can become a source of corrosion of metal vents, plastic piping became the preferred material. Paragraph 12.5.2 of the National Fuel Gas Code requires that plastic vent materials be used for listed gas utilization equipment only when specified in the manufacturer's instructions.

Section 12.5.3 of the National Fuel Gas Code Special Gas Vent

Special gas vent shall be listed and installed in accordance with the special gas vent manufacturer's installation instructions.

All special gas vents are listed vent materials. Special gas vents are listed in accordance with UL 1738, Standard for Venting Systems for Gas-Burning Appliances, Categories II, III and IV. Installation instructions for special gas vents include limitations on operating temperature, categories of appliance to be used with each vent, clearance to combustible materials, types of fittings and joint sealant to be used, and vent termination requirements.

Special attention should be given to the following areas:

1. Proper support for the special gas vent to prevent sagging and to allow for expansion, contraction, and condensate drainage
2. Proper cutting and cleaning of joints and fittings, and the use of recommended joint sealants (substitutes are not usually permitted)
3. Construction of a condensate trap (see the appliance manufacturer's instructions for special requirements)
4. Wall penetrations (the pipe should not be secured at a thimble, because the pipe must be allowed to move to accommodate expansion and contraction)
5. Insulation [the vent pipe or the fittings of the inside of a wall thimble must not be insulated when polymeric (nonmetallic) vent materials are used]

Product Recall

More than 15 years ago, a class of special gas vent known as "high temperature plastic vent" (HTPV) was introduced to the market for use with mid-efficiency appliances. Field experience has shown that these vent systems are prone to failure. The failure may occur because of improper installation practice and/or corrosion from acidic condensate. At this time an active product recall is still under way, with the cooperation of the U.S. Consumer Product Safety Commission, appliance manufacturers, and the vent pipe manufacturers. The product recall covers furnaces that are horizontally vented, as well as all boiler installations. Those who encounter one of these vent systems should call (800) 758-3688 for information on how to proceed. This number is operated by the product manufacturers and will be in operation until the recall is substantially complete. If the number is not in operation, questions can be referred to the furnace, boiler, or water heater manufacturer.

To determine whether the installation has an HTPV pipe system that is subject to this program, the vent pipes attached to the natural gas or propane furnaces or boilers should be checked. Vent pipes subject to this recall program can be identified as follows:

• The vent pipes are plastic.
• The vent pipes are colored gray or black.
• The vent pipes have the names "Plexvent," "Plexvent II," or "Ultravent" stamped on the vent pipe or printed on stickers placed on pieces used to connect the vent pipes together.

The location of those vent pipes should also be checked. For furnaces, only' HTPV systems that have vent pipes that go through the side walls of structures (horizonta1 systems) arc subject to this program. Other plastic vent pipes, such as white PVC or CPVC are not involved in this program.

The Effects of Temperature on PVC Pipe

Polyvinyl Chloride (PVC) is a thermoplastic, and as such, its physical properties change with temperature variations Dimensions, pressure capacity, and stiffness are all affected by temperature changes. The published dimensions and performance ratings for PVC pipe and conduit products are usually applicable only for 73°F. The following will help to explain how PVC pipe and conduit products are affected by operating temperatures other than 73°F.

Dimensions

Like all materials, PVC expands with increasing temperatures and contracts with decreasing temperatures.

The coefficient of thermal expansion for PVC is: 3.0 x 10-5 in/in/°F

Because the length-to-diameter ratios of PVC pipe and conduit products are generally very large, length change from temperature variation is the most noticeable. A good rule of thumb in design of PVC pipe and conduit systems is to allow 3/8" length variation for every 100 feet of pipe for each 10°F change in temperature. (This rule is independent of pipe size.) Table 1 can also be used to determine the effects of temperature changes on the length of PVC pipe and conduit.

NOTE:

THE MAXIMUM RECOMMENDED OPERATING TEMPERATURE FOR PVC PRESSURE PIPE IS 140° (f)

FOR CPVC IT IS 200° (F)

This is reason enough to pay very close attention to flue gas temperatures on a lot of 90+ condensing equipment.

We are now offering our latest manuals Circuitry and Troubleshooting Volume I and Volume II. They are selling for $75.00 for Volume I and $35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a copy + $10.00 shipping and handling. In addition we also have FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and “Venting” it is up to date with the latest changes to the Fuel Gas Code Book. It is also being offered at a price of $75.00 + $10.00 shipping and handling.

We also conduct seminars on the following topics and many others:

• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT

If you are interested in information call 401-437-0557 or write to:

Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net

 

Copyright 2007 — Applied Learning Associates Inc. — All Rights Reserved

  [ home ] seminars ] training team  ] f.a.q. ] testimonials ] sponsors ] tools n' tips  ]